Setup guide · ComAp + DUT-E CAN

Connect a DUT-E CAN fuel level sensor to a ComAp InteliGen4 200

Wire a DUT-E CAN fuel level sensor to the CAN1 port of a ComAp InteliGen4 200 genset controller, set up the sensor, and show fuel level and volume on the controller screen. Tested in 2025.

wagencontrol.eu/compatibility/comap/inteligen4-200-dut-e-can/

Controller
ComAp InteliGen4 200 (8–36 V)
Sensor
DUT-E CAN fuel level sensor (10–45 V)
Interface
CAN J1939, CAN1 port of the controller
Controller software
InteliConfig 2.60.2.2
Sensor software
Service S6 DUT-E 6.05 with the SK S6 adapter kit
Sensors per module
Up to 4 analog values; add a module for more

Wire the sensor to the controller

  1. Connect the CAN H wire of the controller's CAN1 port to CAN H of the DUT-E CAN.
  2. Connect the CAN L wire of CAN1 to CAN L of the DUT-E CAN.
  3. Connect the sensor's brown wire (ground) to the negative terminal of the power supply.
  4. Connect the sensor's orange wire to the positive supply: the sensor accepts 10–45 V.
  5. The InteliGen4 200 itself runs on 8–36 V, so one 12 V or 24 V supply can feed both.
Wiring diagram: two DUT-E CAN sensors connected to the CAN1 port of a ComAp InteliGen4 200 with S6 3SC and S6 SC-CW-700 cables and a 10–36 V power supply
Figure 1. Two DUT-E CAN sensors on the CAN1 port, connected with S6 3SC and S6 SC-CW-700 cables.

Set up the DUT-E CAN

Configure the sensor with the SK S6 adapter kit and the Service S6 DUT-E software (version 6.05). The DUT-E CAN needs only the standard setup:

  • enter the probe length after trimming or extending it,
  • calibrate it for an empty and a full tank,
  • build the tank profile (calibration table), so level is converted to litres.

Give each sensor its own address: 101 for the first, 102 for the second. The controller reads them by these addresses.

Add the sensor to the controller in InteliConfig

Connect the InteliGen4 200 to your computer with a USB cable and start InteliConfig.

  1. In the start window, choose Connect to controller.
  2. Select the connected controller and press OPEN.
  3. Click the Controller Configuration icon.
  4. On the Modules tab, under ECU Modules, choose Add New Module, then User device → Canbus.
  5. In Module Settings, set the Communication Timeout and the module name that the controller screen will show (for example DUT-E CAN). Press Add Module.
  6. Open the J1939 Parameters tab and press + to add a parameter.
InteliConfig start window with Connect to controller highlighted
Figure 2. Start window: Connect to controller.
InteliConfig controller list with the InteliGen4 200 selected and the OPEN button
Figure 3. Select the controller and press OPEN.
InteliConfig main screen with the Controller Configuration icon highlighted
Figure 4. Open Controller Configuration.
Modules tab: Add New Module, User device, Canbus
Figure 5. Modules → Add New Module → User device → Canbus.
Module Settings dialog with Communication Timeout and module name DUT-E CAN
Figure 6. Module Settings: timeout and the name shown on the controller.
J1939 Parameters tab with the + button highlighted
Figure 7. J1939 Parameters: add a parameter with +.
One module holds up to four analog inputs. For more values (for example a third and fourth sensor with level and volume each), add another module the same way; each module gets its own screen on the controller.

Enter the J1939 parameters

In the parameter window, fill in:

FieldWhat to enter
NameParameter name, e.g. Fuel level 1
IO typeAnalog Input
Frame numberThe PGN in raw format, e.g. 0x18F60665: 18 = priority, F606 = PGN 62982, 65 = sensor address 101
PositionStarting byte of the value (from the S6 database and the sensor manual)
LengthLength of the value in bits
DimensionUnit shown on the screen
ResolutionDecimal places shown
FactorScale step
OffsetOffset added to the value

Tested values for two sensors at addresses 101 and 102:

NameFrame numberPositionLength (bits)DimensionResolutionFactorOffset
Fuel level 10x18F606651.116mm0.10.100.0
Fuel volume 10x18F606653.116L0.10.100.0
Fuel level 20x18F606661.116mm0.10.100.0
Fuel volume 20x18F606663.116L0.10.100.0
Four J1939 Parameter dialogs: fuel level and fuel volume for sensors 101 and 102
Figure 8. The four parameters as entered in InteliConfig. Refresh rate stays at 100 ms.

Show fuel level and volume on the controller screen

  1. Open the I/O Configuration tab, select the DUT-E CAN module you created and go to Analog Inputs.
  2. Add each parameter with the + button at the bottom of the screen.
  3. For each one, pick it in the ECU Value list and tick Used in Screens.
  4. Press Write. When asked to log in, enter Username/UID 0001 and Password/PIN 0000 (factory defaults).
  5. The controller saves the configuration and restarts; the values then appear on its screen.
I/O Configuration tab, DUT-E CAN module, Analog Inputs, + button
Figure 9. I/O Configuration → DUT-E CAN → Analog Inputs → +.
Analog input settings with ECU Value and Used in Screens highlighted
Figure 10. Choose the ECU Value and tick Used in Screens.
Authorization window after pressing Write
Figure 11. Write the configuration and log in.

Check the readings

Compare the controller screen with Service S6 DUT-E: level and volume must match for each sensor. In the test, the controller showed 687.8 mm / 639.1 L for sensor 1 and 70.7 mm / 617.8 L for sensor 2, the same as the service software.

Controller display with fuel level and volume next to the same values in Service S6 DUT-E
Figure 12. Controller screen (left) and Service S6 DUT-E (right) show the same values.

Last updated 26 November 2026.

Setting up ComAp InteliGen4 200 + DUT-E CAN?

Send us your tracker firmware, the server you use and a screenshot of the settings. An engineer checks the setup and helps with the calibration.