Connect a DUT-E CAN fuel level sensor to a ComAp InteliGen4 200
Wire a DUT-E CAN fuel level sensor to the CAN1 port of a ComAp InteliGen4 200 genset controller, set up the sensor, and show fuel level and volume on the controller screen. Tested in 2025.
wagencontrol.eu/compatibility/comap/inteligen4-200-dut-e-can/
- Controller
- ComAp InteliGen4 200 (8–36 V)
- Sensor
- DUT-E CAN fuel level sensor (10–45 V)
- Interface
- CAN J1939, CAN1 port of the controller
- Controller software
- InteliConfig 2.60.2.2
- Sensor software
- Service S6 DUT-E 6.05 with the SK S6 adapter kit
- Sensors per module
- Up to 4 analog values; add a module for more
Wire the sensor to the controller
- Connect the CAN H wire of the controller's CAN1 port to CAN H of the DUT-E CAN.
- Connect the CAN L wire of CAN1 to CAN L of the DUT-E CAN.
- Connect the sensor's brown wire (ground) to the negative terminal of the power supply.
- Connect the sensor's orange wire to the positive supply: the sensor accepts 10–45 V.
- The InteliGen4 200 itself runs on 8–36 V, so one 12 V or 24 V supply can feed both.

Set up the DUT-E CAN
Configure the sensor with the SK S6 adapter kit and the Service S6 DUT-E software (version 6.05). The DUT-E CAN needs only the standard setup:
- enter the probe length after trimming or extending it,
- calibrate it for an empty and a full tank,
- build the tank profile (calibration table), so level is converted to litres.
Give each sensor its own address: 101 for the first, 102 for the second. The controller reads them by these addresses.
Add the sensor to the controller in InteliConfig
Connect the InteliGen4 200 to your computer with a USB cable and start InteliConfig.
- In the start window, choose Connect to controller.
- Select the connected controller and press OPEN.
- Click the Controller Configuration icon.
- On the Modules tab, under ECU Modules, choose Add New Module, then User device → Canbus.
- In Module Settings, set the Communication Timeout and the module name that the controller screen will show (for example
DUT-E CAN). Press Add Module. - Open the J1939 Parameters tab and press + to add a parameter.






Enter the J1939 parameters
In the parameter window, fill in:
| Field | What to enter |
|---|---|
| Name | Parameter name, e.g. Fuel level 1 |
| IO type | Analog Input |
| Frame number | The PGN in raw format, e.g. 0x18F60665: 18 = priority, F606 = PGN 62982, 65 = sensor address 101 |
| Position | Starting byte of the value (from the S6 database and the sensor manual) |
| Length | Length of the value in bits |
| Dimension | Unit shown on the screen |
| Resolution | Decimal places shown |
| Factor | Scale step |
| Offset | Offset added to the value |
Tested values for two sensors at addresses 101 and 102:
| Name | Frame number | Position | Length (bits) | Dimension | Resolution | Factor | Offset |
|---|---|---|---|---|---|---|---|
| Fuel level 1 | 0x18F60665 | 1.1 | 16 | mm | 0.1 | 0.10 | 0.0 |
| Fuel volume 1 | 0x18F60665 | 3.1 | 16 | L | 0.1 | 0.10 | 0.0 |
| Fuel level 2 | 0x18F60666 | 1.1 | 16 | mm | 0.1 | 0.10 | 0.0 |
| Fuel volume 2 | 0x18F60666 | 3.1 | 16 | L | 0.1 | 0.10 | 0.0 |

Show fuel level and volume on the controller screen
- Open the I/O Configuration tab, select the DUT-E CAN module you created and go to Analog Inputs.
- Add each parameter with the + button at the bottom of the screen.
- For each one, pick it in the ECU Value list and tick Used in Screens.
- Press Write. When asked to log in, enter Username/UID 0001 and Password/PIN 0000 (factory defaults).
- The controller saves the configuration and restarts; the values then appear on its screen.



Check the readings
Compare the controller screen with Service S6 DUT-E: level and volume must match for each sensor. In the test, the controller showed 687.8 mm / 639.1 L for sensor 1 and 70.7 mm / 617.8 L for sensor 2, the same as the service software.

Last updated 26 November 2026.